Part Number Hot Search : 
Q3350 FSP3125 SCF20C60 100B1T KP100A MAX122 HMC291SE BZX84C3
Product Description
Full Text Search
 

To Download DR-75-24 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 DR-75
Input Parameter
Series
New Industrial Supplies!!
Conditions Min. 85 120 47 Typ. Max. 264 370 63 Units VAC VDC Hz A 1.0 Min. 12 24 48 0.5 1.0 1,000 1,800 60 60 12 100 150 240 150 16.5 36 60 90 Typ. 1.0 Max. 14 28 53 mA Units % VDC % % mSec mSec mSec mV Pk-Pk % VDC C %/C kHz Units VAC M
Low Cost, Industrial 75W, DIN Rail Mount AC/DC Power Supplies
Electrical Specifications
Specifications typical @ +25C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Key Features:
* 75W Output Power * DIN Rail Mountable * Universal AC Input * UL 508 Approved * Safety Approved * 12, 24 & 48 VDC Outputs * Cond./Rad. EMI Class B * >120 kH MTBF * LOW COST!
Input Voltage Range Input Frequency Range Inrush Current Leakage Current Output Parameter Output Voltage Tolerance Voltage Adjustment Range Line Regulation Load Regulation Set Up Time Rise Time Hold Time Ripple & Noise (Note 2) Output Power Protection Over Voltage Protection (Note 4) Over Temperature Protection Temperature Coefficient Switching Frequency General Parameter Isolation Voltage 230 VAC, Cold Start 115 VAC, Cold Start 240 VAC Conditions Note 1 12 VDC Output 24 VDC Output 48 VDC Output Iout = 10% to 100% 230 VAC, Full Load 115 VAC, Full Load At Full Load 230 VAC, Full Load 115 VAC, Full Load 12 VDC Output 24 VDC Output 48 VDC Output Note 3 12 VDC Output 24 VDC Output 48 VDC Output Note 5 0C to 50C Fixed Conditions Input - Output Input - FG (Frame Ground) Output - FG (Frame Ground) 500 VDC Conditions
40 20
105 15 30 54 80
85 0.03 50 Typ.
RoHS Compliant
MicroPower Direct
232 Tosca Drive Stoughton, MA 02072 USA T: (781) 344-8226 F: (781) 344-8481 E: sales@micropowerdirect.com W: www.micropowerdirect.com Isolation Resistance (Note 6) Environmental Parameter Operating Temperature Range Storage Temperature Range Operating Humidity Storage Humidity Vibration Physical Case Size Case Material Connection Weight Reliability Specifications Parameter MTBF Safety Standards Safety Approvals EMI Compliance Harmonic Current Compliance EMS Immunity Compliance
Min. 3,000 1,500 500 100
Max.
Min. Typ. Max. Units -10 +25 +60 C -20 +85 C RH, Non-condensing 20 90 % RH, Non-condensing 10 95 % 10 ~ 500 Hz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour Ambient 2.18 x 4.93 x 3.94 Inches (55.5 x 125.5 x 100.0 mm) Aluminum Screw Terminal 21 Oz (0.6 kg)
Min. Typ. Max. Units 123.1 kHours UL 508, UL 60950, EN 60950-1 UL, cUL, TUV Compliance to EN55011, EN55022 (CISPR22) Class B Compliance to EN6100-3-2,-3 EN6100-4-2,3,4,5,6,8,11; ENV50204;EN6100-6-2(EN50082-2) Heavy Ind. Level, criteria A
Conditions MIL HDBK 217F, 25C, Gnd Benign
Model Selection Guide
Model Number DR-75-12 DR-75-24 DR-75-48 Rated Power (W) 76 76.8 76.8 Input Voltage (VAC) Range 85 - 264 85 - 264 85 - 264 Current (A) 115 VAC 1.6 1.6 1.6 230 VAC 0.96 0.96 0.96 Voltage (VDC) 12 24 48 Output Current (A) Max) 6.3 3.2 1.6 Current (A) Range 0 ~ 6.3 0 ~ 3.2 0 ~ 1.6 Efficiency (%, Typ) 76 80 81 Fuse Rating Slow-Blow (A) 5.0 5.0 5.0
Notes: 1. Output voltage tolerance includes set-up tolerance, line regulation and load regulation. For the 12V output model, tolerance is 2.0%. 2. Ripple & noise is measured using equipment with 20 Mhz of bandwidth. Connection to the unit under test is made with a 12 inch length of "twisted pair" wires terminated with a set of 1.0 F & 4.7 F capacitors connected in parallel. 3. Overload protection is foldback current limiting. The unit recovers automatically when the fault is removed. 4. Over voltage protection is a clamp type. The power to the unit must be manually reset to recover. 5. Over temperature protection shuts down the output. The unit recovers automatically when the temperature goes down. The thermal detector is mounted on the heat sink of the power semiconductor. 6. Isolation resistance is given for Input/Output; Input/FG and Output/FG. 7. To mount the unit to the DIN rail, tilt the unit rearwards from the top, fitting the mount over the top of the rail. Press back on the bottom front of the unit until it locks in place on the rail. To remove the unit from the rail, pull the removal clip at the bottom rear of the unit downward with a screw driver. With the clip down, lift up on the unit from the bottom front until it clears the rail. Before installation or removal all wiring should be disconnected and the main power to the system shut off. 8. When wiring the supply, all lines should be as thick and short as possible. AWG 14 wire is recommended for the DR-75 series. 9. The units should be mounted so they are vertically orientated. Air flow (if it is provided) would optimally flow from the bottom to the top of the unit. 10. It is recommended that a fuse be used on the input of a power supply for protection. See the table above for the correct rating.
Derating Curve - Output Power vs Ambient Temperature
Derating Curve - Output Power vs Input Voltage
Mechanical Dimensions
Terminal Connections - TB1
Pin 1 2 3 Function Frame Ground (FG) AC/Neutral (DC+) AC/Live (DC-)
Terminal Connections - TB2
Pin 1,2 3,4 Function DC Output (+V) DC Output (-V)
Mechanical Notes:
* All dimensions are typical in inches (mm) * Tolerance x.xx = 0.01 (0.25)
MicroPower Direct
www.micropowerdirect.com
232 Tosca Drive Stoughton, MA 02072
*
TEL: (781) 344-8226
*
FAX: (781) 344-8481
*
E-Mail: sales@micropowerdirect.com


▲Up To Search▲   

 
Price & Availability of DR-75-24

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]